Technical manual - air-water monobloc heat pump
TECHNICAL INSTALLATION AND MAINTENANCE MANUAL
MONOBLOC AIR-WATER HEAT PUMP
MODEL TERMOCASA TMC MA9 HYPER-JET


Congratulations!
You are the owner of a TMC HYPER-JET heat pump. In this manual you can find out how to use this heat pump.
Keep this manual as it contains installation and maintenance instructions. This product is designed to work over a long period of time. To use and maintain the product in optimal operating conditions, it is necessary to keep the manual.
ATTENTION !!!
WHEN STARTING THE HEAT PUMP, HAVE A DEVICE FOR MEASURING THE ELECTRICAL VOLTAGE AND A NON-CONTACT THERMOMETER.
Why choose the pumps produced by the company TERMOCASA?
- Heat pumps TERMOCASA incorporates technologies and materials invented and patented in Romania by Romanian engineers;
- Heat pumps TERMOCASA benefits from very long warranty periods and ultra-fast service due to the increased reliability and attention to the customer;
- Heat pumps TERMOCASA benefits from the most efficient ULTRAFLEX flexible heat exchangers on the market - invented in Romania;
- Heat pumps TERMOCASA they have performances hard to match even the most well-known brands of heat pumps.
| Technical data | TMC MA9 Hyper-Jet |
|---|---|
| Rated input power kw/h | 0,16-3,1 |
| Heating power kw/h | 1,6-8,8 |
| Minimum operating temperature (°C). | -30 |
| SCOP compressor performance coefficient max | 5.1 |
| Noise level (decibels) | <60 |
| Compressor | Full DC Inverter |
| V / Hz power supply | 230/50 |
| Refrigerant (optionally added) | R32 |
| Ultraflex heat exchanger (galvanic optional) | Pipe in pipe |
| Pressure protection | HP / LP |
| Internet or radio control | Optional |
| Transport weight Kg | 59 |
| Internal unit dimensions/dimensions cm (without rear connections) | H90-L90-A36 |
Environmental protection is a priority for the group TERMOCASA.
Product quality, efficiency and environmental protection, all these are equally important objectives for us. Environmental protection laws and regulations are strictly followed.
We use the best techniques and materials for environmental protection, while also taking into account economic points of view.
An easy-to-use heat pump
The TMC HYPER-JET heat pump uses air heat capture as the primary source, using the captured energy to heat your building. The heat pump can be connected to the heating system of the building as well as to a boiler for domestic hot water.
Important!
When delivering and installing the product, carefully check the following important points:
- The TMC HYPER-JET heat pump must be placed and transported in an upright position;
- Check whether or not the product has been hit during transport;
- If blows are observed, report them to the carrier and supplier;
- Place the TMC HYPER-JET heat pump on a straight surface made of concrete or other rigid materials, or on a support fixed to the wall.
Transport
- The product must be transported and stored in an upright position.
- To avoid impact during transport, do not unpack the product until it reaches the room and the place where you want to mount it.
- The heat pump can be operated with a forklift or manually with special care.
Unpacking
- Unpack the heat pump only after bringing it close to the area where it will be installed. Check that the product has been hit during transport. Report any wear and tear caused by transport from the contracted supplier.
Safety instructions
These instructions must be read before handling, installing and using the heat pump.
- Make sure the product is unplugged before any intervention.
- When mounting the product, if a clamping / moving device is used, first check it for wear and tear that could endanger the product or the installer.
- Do not post under the product while it is suspended.
- Do not endanger yourself by attempting to disassemble the product casing.
- Do not endanger yourself by connecting the equipment to worn or incorrectly sized electrical fuses.
- Work on the electrical panel or heat circuit must only be carried out by authorized persons.
- This appliance is filled with flammable R32 refrigerant. Improper use of the device leads to risks of serious personal injury and property damage, for this reason installation must only be done by authorized persons.
TMC HYPER-JET heat pump installation options
- The heat pump can be installed to serve both the heating/cooling air conditioning system of the house as well as one or more boilers for heating domestic hot water.
- The TMC HYPER JET heat pump has no user-made settings but is automatically set to meet your needs.
- The command and control elements inside the heat pump can only be accessed by an authorized person.
- After the authorized installer has completed the installation of the pump, check the installation together. Allow the installer to show you how to start and maintain the heat pump so that you can understand the principle of operation.
- The heat pump is switched off using the thermostat installed by your installer on the outside of the heat pump or disconnected from the power supply.
- The heat pump is equipped with a compressor shut-off system that is triggered in the event of an electrical overload, and the cause of such an error may be:
- The compressor is overloaded – Contact a technician.
- Defective compressor – Contact a technician.
- Shutdown due to electrical overload – Contact a technician.
Product installation
This chapter is dedicated to those who are authorized to install the product (authorized plumber/electrician) so that the TMC HYPER JET heat pump works properly to the parameters required by the owner. In any case, the user has all the necessary information in this manual to be able to understand and use the purchased product correctly.
Outdoor unit
Dimensions: H 900mm, L 914mm, A 363mm


Electrical and hydraulic connections:

1) control cable, 2) 230V power cable, 3) Recirculation pump power cable 230V, 4) Refrigerant connection.
Rear view:

1) Heat outlet, 2) Heat input, 3) Temperature sensor (pre-installed), 4) Refrigerant connection.
Product installation recommendations
The connecting pipes must be insulated with at least 10mm of insulation.
At the connection (heating agent outlet) it is recommended to install an air vent to remove air from the installation
DO NOT ALLOW THE SIGNAL CABLE TO INTERFER WITH OTHER CABLES. Using vinyl tape, secure the electrical cables and coolant pipes. DO NOT WRAP THE PIPE ENDS only after performing leak tightness tests.
When mounting the external unit, you must be careful when passing the heating agent pipes through the hole in the wall, check that the ends of the heating agent pipes are sealed to prevent dirt or impurities from entering the pipes. Slowly pass the heating agent pipes and electrical cables through the hole in the wall.
LIMITS REGARDING THE LENGTH AND LEVEL DIFFERENCE OF THE PIPES.The length of the pipes between the outdoor unit and the interior of the building must be as short as possible, increasing the overall efficiency of the device.
INSTALLATION OF THE EXTERNAL UNIT
When choosing the installation location of the outdoor unit, consider the following:
Before starting the installation, check that the external drive has been transported in an upright position. If this has not happened, position it correctly and wait at least two hours before starting it. If possible, position the unit away from rain and direct sunlight, in an area with sufficient ventilation. Place the unit in a location where there are no support problems and where vibration and noise cannot be amplified. Position it so that the operating noise and airflow do not disturb the neighbors. Position it respecting the minimum distances from walls, furniture or other objects that may exist around (fig. 6 and fig. 7). If the installation takes place on the ground, avoid areas with risk of water accumulation or falls, formation of ditches, etc. In areas with a lot of snow or where the temperature remains below 0°C for long periods, install the unit on a 20-30 cm cement base to prevent snow from accumulating around the unit. In winter, heat pumps produce condensation, which falls on the supporting surface, forming water deposits that are sometimes disturbing and/or unpleasant. The air conditioning installation must not be surrounded by more than three walls, in order to ensure the ventilation necessary for proper operation.


OUTDOOR UNIT INSTALLATION
Mount the external unit on a rigid support to prevent increased noise and vibration levels. To present weather shields for protection against sunlight and rain. Make sure there is no obstacle blocking the discharged air. Do not install near public access streets, crowded areas, or where the noise from the unit will disturb those around or near animals or plants that would be affected by the exhaust air, away from any source of flammable gases. If the unit is exposed to strong wind: install the unit so that the fan discharge is at a 90° angle to the wind direction.
If the unit is frequently exposed to heavy rain or snow, install a cover above the unit to protect the unit from rain or snow, otherwise the heat pump will perform repeated defrosts. Be careful not to obstruct the flow of air around the unit. Before attaching the outdoor unit to the established location, you must install a drain connection at its bottom. There are two types of drain connections depending on the type of external unit. Connect the drain hose (not included) to the drain connection to divert water to the front of the unit during heating mode.
Hydraulic connection
The installation of the product must be done carefully taking into account the installation standards and the building plan. The product must be connected to an expansion vessel in a closed system. Remember to clean the radiators of rust and other debris before mounting.
Complete all installation / adjustment steps according to the description in the installation chapter "Commissioning the product".
The flow and return pipes of the heating medium circuit must have a recommended diameter of 32 mm.
The heat pump can work with temperatures up to approximately 50°C on the return and returns on the circuit (tour) maximum temperatures of 65°C for short periods of time (0-3 hours for boiler water heating), and the operating temperature continues (normal) of the heat pump must not exceed 40 degrees Celsius on the return and 45 degrees Celsius on the heating medium.
Circulation pump
The circulation pump (recommended minimum 25-11) for the heating / cooling agent must be dimensioned so that it can ensure a temperature difference of the thermal agent between flow and return between 3 and 7 degrees Celsius to ensure an optimal operation of the heat pump. .
Make sure that a sufficiently large circulation pump has been installed so as to provide the heat pump with sufficient heating medium.
airing
- There must be no air in the circuit. Even the smallest air bubbles can affect the proper functioning of the product.
- After charging the heating system with liquid, check if there is a background noise from the pump, check if it has been completely bled.
- Add water/antifreeze if necessary to reach the correct pressure, i.e. between 1,5 and 3 bar.
Electric instalation
The electrical installation and installation of the heat pumps must be carried out by an authorized electrician. All cable connections must be made in accordance with the relevant rules and regulations.
The electrical and data transmission connection between the outdoor unit and the interior of the building is made with a cable according to the specifications below and each one is connected to its correspondent as can be seen in the images above.
At the L, N and grounding connection, connect the power supply cable to be connected to the outlet inside the building.
Please pay special attention to these electrical connections because if there are imperfect contacts then malfunctions can occur.
BEFORE CARRYING OUT THE ELECTRICAL CONNECTIONS, READ THESE REGULATIONS
All connections must comply with local and national codes and must be installed by a licensed electrician. All electrical connections must be made according to the Electrical Connections Scheme located on the panels of the internal and external units. If there is a serious safety problem with the power supply, stop operation immediately. Explain to the customer the reason for this interruption and refuse to install the unit until the safety reason has been properly resolved. The supply voltage must be between 95-100% of the nominal voltage. Insufficient power supply may cause malfunction, electric shock or fire. If the power supply is connected by fixed cables, install a surge protector and a switch on the main power supply with a capacity of 1,5 times the current of the unit. If the electrical supply is connected via fixed cables, a switch or a switch that disconnects all poles and has a separation contact of at least 3mm must be included in the fixed wiring. The unit should only be connected to an individual branch output of the circuit. Do not connect other equipment to that output.
Make sure you have properly grounded the heat pump Termocasa.
Each cable must be securely fastened. Loosen the wiring that may cause the terminal to overheat, resulting in product failure and possible fire. Do not allow cables to touch or sit on the refrigerant pipe, compressor, or many moving components in the unit.
WARNING BEFORE MAKING ANY ELECTRICAL CONNECTIONS: DISCONNECT THE MAIN ELECTRICAL POWER SUPPLY TO THE SYSTEM.
- Connect the control cable that allows communication between the internal thermostat and the external unit. You must first choose the correct cable size before preparing it for connection.
- Power cables for external unit: H07RN-F 3x4mmp
- Signal cable: H07RN-F 2×2,5mmp
- BE CAREFUL WITH THE PHASE CABLES! While crimping the cables, ensure that Live ("L") is clearly distinguished from the other cables and do not reverse the Live and Neutral cables. This would be dangerous and may cause the heat pump to malfunction Termocasa.
- Wrap pipes and cables. Before passing the pipes and signal cables through the hole in the wall, you should tie them together to take up less space, protect and insulate them.
Power source
The TMC HYPER-JET heat pump must be connected to 230V or 400V, uninterruptible power supply, protected with grounding.
If the voltage at the equipment's power outlet is not stable, it is recommended to check and fix the problem or use a voltage stabilizer that must be 4× the equipment's power, and capable of supporting the current and voltage at startup and during equipment operation.
Safety switch
The electrical installation must contain a safety switch for the complete interruption of the electrical energy.
IMPORTANT!
The heat pump has maximum efficiency and low consumption when:
- the temperature difference between return and return is between 3 and 7 degrees Celsius
- the insulation of all contact surfaces of the building with the outside should be as good as possible (the equivalent of a polystyrene of at least 10 cm)
- the radiant surfaces (radiator, floor, fan coil units, etc.) should be as large as possible so that the temperature of the heating agent (35-45 degrees Celsius per round) is sufficient for heating the building.
- The service period and inspection of the heat pump for the maintenance of the warranty periods, ie the inspection and replacement of certain components if necessary, must not exceed 2 calendar years regardless of the type of warranty.
Caution!
The heat pump can only operate in stationary heating or domestic hot water mode if the outside temperature does not exceed 37 degrees Celsius, to protect the compressor from overheating. If the outside temperature exceeds 37 degrees Celsius, it is recommended to use the electric heater from the boiler to prepare domestic hot water.
Wiring diagram heat pump + boiler + building heating:
1) boiler thermostat, 2) 3-way solenoid valve TERMOCASA, 3) ambient thermostat, 4) heat pump, 5) heat pump supply, 6) recirculation pump, 7) 3-way boiler / valve thermostat supply.

HEAT PUMP ASSEMBLY DIAGRAM WITH INTERMEDIATE EXCHANGER
1) heat agent output to the building or boiler, 2) heat agent input from the building or boiler, 7) intermediate recirculation pump, 8) heat pump thermal agent output, 9) heat pump thermal agent input, 10) intermediate heat exchanger, 11) heat pump, 12) real estate recirculation pump

ASSEMBLY SCHEME 2 HEAT PUMPS WITH PUFFER AND BOILER
5) heat pump, 6) 3-way solenoid valve Termocasa, 7) recirculation pump, 8) domestic hot water boiler, 9) hot water outlet boiler, 10) cold water boiler inlet, 11) storage tank (buffer), 12) building heating circuits.

HEAT PUMP ASSEMBLY SCHEME WITH PUFFER AND BOILER
5) heat pump, 6) recirculation pump, 7) 3-way solenoid valve Termocasa, 8) hot water outlet boiler, 9) domestic hot water boiler, 10) cold water boiler inlet, 11) storage tank (buffer), 12) building heating circuits

BOILER HEAT PUMP ASSEMBLY SCHEME
5) heat pump, 6) recirculation pump, 7) 3-way solenoid valve Termocasa, 8) hot water outlet boiler, 9) domestic hot water boiler, 10) cold water boiler inlet, 11) building heating circuits

Heat pump installation diagram with puffer, boiler and solar panel
1) thermal power plant, 2) DHW (domestic hot water) boiler, 3) recirculation pump, 4) 3-way solenoid valve, 5) recirculation pump, 6) gravity direction flap, 7) solar panel, 8) recirculation pump, 9) building heating circuits, 10) storage tank (buffer)
The 3-way solenoid valve (4) from the green circuit and the recirculation pump (5) will be supplied from the solar panel automation.

Heat pump installation diagram with puffer, boiler and solar panel (with intermediate exchanger)
5) heat pump, 6) recirculation pump, 7) 3-way solenoid valve Termocasa (2 pcs.), 8) hot water outlet boiler, 9) domestic hot water boiler, 10) cold water boiler inlet, 11) storage tank (buffer), 12) building heating circuits, 13) sense flap, 14) recirculation pump, 15) solar panel with direct absorption, 16) intermediate heat exchanger, 17) recirculation pump, 18) recirculation pump.
The 3-way valve (7) on the green circuit and the recirculation pump (18) will be supplied from the solar panel automation.

RECOMMENDATIONS:
- Recirculation pumps must be at least 25-11 (connection 25, pressure 1,1 bar) and set at maximum speed
- In the case of zone heating, it is recommended to use a puffer to avoid continuous operation of the heat pump.
- After the installation is completed, all modules will be powered/started, the top cover of the external unit will be opened, the remote control will be pointed inside the external unit, and the on/off button will be pressed from the remote control to activate the heat pump, the arrow will be pressed up until it reaches 30 degrees, and the MODE button will be pressed until AUTO is displayed on the remote control.
- In heating circuits where heat pumps are used, it is recommended to avoid the use of mixing valves at the distributors in the building and to avoid the use of equalization cylinders on the hydraulic circuits.
- The TMC 3-way valve can be installed both on the flow and on the return because we have temperatures below 60 degrees Celsius.



- Flows or returns from heat pumps (if there are 2 or more) do not connect more than one heat pump to the same buffer connection, the flow is connected to the highest connection, and the return to the lowest of the buffer.
- The supply voltage must be 230v or 400v (230v on each phase) both at the start of the heat pump and during operation with a tolerance of +/- 5%.
- Before starting the heat pump, the circuits must be checked so that there are no closed taps or the 3-way valve is not blocked in a position that blocks the passage of the heat agent.
- When starting the heat pump for the first time, it is recommended to use a normal socket to power the recirculation pump and the ground water pump, and after setting the thermostats (boiler and puffer), the pumps should be powered from the socket mounted on the heat pump housing.
- The temperature difference between flow (hot outlet) and return (hot inlet) should be approximately 5-7 degrees Celsius.
- For accurate temperature measurement, a non-contact thermometer will be used and the reading will be performed on metal surfaces previously covered with electrical insulating tape or non-reflective paint.
- The heat pump exchangers, from the moment of starting use, must be constantly immersed in water/liquid, otherwise there is a risk of damage and even cracking.
- The surface of the coil in the boiler must be a minimum of:
- 3 sqm for a 24kw pump,
- 2,5 sqm for a 18kw pump,
- 2 sqm for a 12kw pump,
- 1,5 sqm for a 6kw pump.
- A maximum 3 bar safety valve must be installed on the two circuits.
- If the puffer is not used, the temperature difference between the flow (hot outlet) and return (hot inlet) will be checked, and if it is greater than 7 degrees due to the undersizing of the home's heating system, then it will be used on the return a stronger recirculation pump or hydrophore pump if applicable.
- In the case of using radiators/radiators/fan coil units, they must have 1kw nominal power for every 3-5 m20 of heated building, i.e. for a 4 m6 room you need XNUMX-XNUMXkw (nominal power).
Declaration of conformity
The company declares that this appliance complies with the requirements of the following directives and subsequent amendments:
- Low Voltage Directive 2014/35 / EU;
- Electromagnetic Compatibility Directive 2014/30/EU;
- EU Directive 2012/19 / WEEE;
- RoHS Directive 2011/65 / EU.
- Directive 2009/125 / EC ErP
- EU Regulation on energy labeling 2017/1369;
And they are in accordance with the requirements of the Norm:
- EN 60335-2-40

Troubleshooting
Safety
Careful! The capacitors are electrically charged, even if the power supply is turned off. Don't forget to discharge the current into the capacitor.

For other models, please connect the discharge resistor (about 100Ω 40W) or soldering iron (plug) between the +, – terminals of the electrolytic capacitor on the opposite side of the outer PCB.

Note: The image above is for reference only. The side plug may be different.
1. Indoor unit error display
| Operation lamp | Timer lamp | Display | Status LED |
|---|---|---|---|
| ☆ 1 time | X | E0 | EEPROM internal drive parameter error |
| ☆ 2 times | X | E1 | Communication error of indoor / outdoor units |
| ☆ 4 times | X | E3 | The speed of the indoor fan got out of hand |
| ☆ 5 times | X | E4 | Indoor room temperature sensor T1 – open circuit or short circuit |
| ☆ 6 times | X | E5 | Evaporator coil temperature sensor T2 – open circuit or short circuit |
| ☆ 7 times | X | EC | Detection of refrigerant leaks |
| ☆ 1 time | O | F0 | Overload current protection |
| ☆ 2 times | O | F1 | Outdoor ambient temperature sensor T4 – open circuit or short circuit |
| ☆ 3 times | O | F2 | Capacitor coil temperature sensor T3 – open circuit or short circuit |
| ☆ 4 times | O | F3 | Compressor temperature discharge sensor T5 – open circuit or short circuit |
| ☆ 5 times | O | F4 | Outdoor unit EEPROM parameter error |
| ☆ 6 times | O | F5 | The speed of the outdoor fan was out of control |
| ☆ 1 time | ☆ | P0 | IPM failure or IGBT current protection too strong |
| ☆ 2 times | ☆ | P1 | Overvoltage or low voltage protection |
| ☆ 3 times | ☆ | P2 | High temperature protection of the IPM module or compressor |
| ☆ 5 times | ☆ | P4 | Inverter compressor unit error |
1.2 Troubleshooting
1.2.1 Diagnosis and troubleshooting of EEPROM parameters (E0 / F4)
| Error code | E0 / F4 |
|---|---|
| Failure decision | The main inner or outer PCB chip does not receive feedback from the EEPROM chip. |
| Alleged causes | ● Installation error ● Defective PCB |
Troubleshooting:

EEPROM: a read-only memory whose contents can be deleted and reprogrammed using a voltage pulse. For the location of the EEPROM chip, please see the photos below.

Note: The two photos above are for reference only, they may not be exactly the same as the ones you have.
1.2.2 Diagnosis and communication solution of the indoor / outdoor unit (E1)
| Error code | E1 |
|---|---|
| Conditions for decision of malfunction | The indoor unit does not receive feedback from the outdoor unit for 110 seconds and this condition happens four times continuously. |
| Alleged causes | ● Wiring error ● Defective internal or external PCB |
Troubleshooting:

1.2.3 Fan speed out of control – diagnosis and solution (E3)
| Error code | E3 / F5 |
|---|---|
| Failure decision conditions | When the speed of the indoor fan remains too low (300RPM) for a certain period of time, the unit will turn off and the LED will display the fault. |
| Alleged causes | ● Wiring error ● The fan is defective ● The fan motor is defective ● Defective PCB |
Troubleshooting:

Index1:
1: Indoor or outdoor DC fan motor (control chip is in the fan motor)
Also start when the unit is in standby mode, measure the voltage pin1-pin3, pin4-pin3 in the fan motor connector. If the voltage value is not in the range shown in the table below, the PCB must be in trouble and must be replaced.

DC motor voltage input and output
| No. | Color | Signal | Voltage |
|---|---|---|---|
| 1 | Red | Vs / Vm | 280V to 400V |
| 2 | - | - | - |
| 3 | Black | GND | 0V |
| 4 | White | Vcc | 14-17.5V |
| 5 | Yellow | Vsp | 0~5.6V |
| 6 | Blue | FG | 14-17.5V |
2. External DC fan motor (control chip is in external PCB)
Start and check if the fan can operate normally, if the fan can operate normally, the PCB should have problems and need to be replaced. If the fan cannot operate normally, measure the resistance of each of the two pins. If the resistance is not equal to each other, the fan motor must have problems and must be replaced, otherwise the PCB must have problems and must be replaced.
3. Indoor AC fan motor
Turn on and set the unit to operate in fan mode at high fan speed. After running for 15 seconds, measure the voltage of pin 1 and pin 2. If the voltage value is less than 100V (208 ~ 240V power supply) or 50V (115V power supply), the PCB has problems and needs to be replaced.
1.2.4 Temperature sensor open circuit or short circuit – diagnosis and solution (E5)
| Error code | E4/E5/F1/F2/F3 |
|---|---|
| Failure decision conditions | If the sampling voltage is less than 0,06V or greater than 4,94V, the LED will display the fault. |
| Alleged causes | ● Wiring error ● Defective sensor |
Troubleshooting:


1.2.5 Refrigerant leak detection – diagnosis and solution (EC)
| Error code | EC |
|---|---|
| Failure decision conditions | Define the temperature of the evaporator coil T2 of the compressor starts running as Tcool. At first 5 minutes after starting the compressor, if T2 |
| Alleged causes | ● Defective T2 sensor ● Internal PCB is defective ● System problems, such as leaks or blockages. |
Troubleshooting:

1.2.6 Diagnosis and current overload protection solution (F0)
| Error code | F0 |
|---|---|
| Failure decision conditions | An abnormal increase in current is detected by checking the specified current detection circuit. |
| Alleged causes | ● Power problems ● System lock ● Defective PCB ● Wiring error ● Compressor malfunction |
Troubleshooting:

1.2.7 IPM malfunction or diagnostics and too strong IGBT current protection solution (P0)
| Error code | P0 |
|---|---|
| Failure decision conditions | When the voltage signal sent by the IPM to the compressor control unit is abnormal, the display LED will display “P0” and the AC will turn off. |
| Alleged causes | ● Wiring error ● IPM failure ● The outdoor fan is defective ● Compressor malfunction ● External PCB is defective |
Troubleshooting:

> IPM continuity check
Turn off the power, allow the high capacity electrolytic capacitors to completely discharge and disassemble the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N.

1.2.8 Diagnosis and protection solution against overvoltage or overvoltage (P1)
| Error code | P1 |
|---|---|
| Failure decision conditions | An abnormal increase or decrease in voltage is detected by checking the specified voltage detection circuit. |
| Alleged causes | ● Power problems. ● Leaking or blocking the system ● Defective PCB |
Troubleshooting:

1.2.9 IPM or Compressor High Temperature Protection – Diagnosis and Solution (P2)
| Error code | P2 |
|---|---|
| Failure decision conditions | If the sampling voltage is not 5V, the LED will display the fault. |
| Alleged causes | ● Power problems ● System leaks or blockages ● Defective PCB ● Connection problems |
Troubleshooting:

Compressor high temperature protection:


1.2.10 Inverter compressor unit error – diagnosis and solution (P4)
| Error code | P4 |
|---|---|
| Failure decision conditions | An abnormal unit of the inverter compressor is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation signal detection and so on. |
| Alleged causes | ● Wiring error ● IPM failure ● The outdoor fan is defective ● Compressor malfunction ● External PCB is defective |
Troubleshooting:

Checking the main parts
1. Check the temperature sensor
Disconnect the temperature sensor from the PCB, measure the resistance value with a tester.

Temperature sensors.
- Room temperature sensor (T1),
- Inner coil temperature sensor (T2),
- Outer coil temperature sensor (T3),
- Outdoor ambient temperature sensor (T4),
- Compressor discharge temperature sensor (T5).
- Measure the resistance value of each winding using the multimeter.
Temperature sensor resistance value table for T1, T2, T3, T4 (°C – -K)
| ° C | ° F | K Ohm | ° C | ° F | K Ohm | ° C | ° F | K Ohm | ° C | ° F | K Ohm |
|---|---|---|---|---|---|---|---|---|---|---|---|
| -20 | -4 | 115.266 | 20 | 68 | 12.6431 | 60 | 140 | 2.35774 | 100 | 212 | 0.62973 |
| -19 | -2 | 108.146 | 21 | 70 | 12.0561 | 61 | 142 | 2.27249 | 101 | 214 | 0.61148 |
| -18 | 0 | 101.517 | 22 | 72 | 11.5 | 62 | 144 | 2.19073 | 102 | 216 | 0.59386 |
| -17 | 1 | 96.3423 | 23 | 73 | 10.9731 | 63 | 145 | 2.11241 | 103 | 217 | 0.57683 |
| -16 | 3 | 89.5865 | 24 | 75 | 10.4736 | 64 | 147 | 2.03732 | 104 | 219 | 0.56038 |
| -15 | 5 | 84.219 | 25 | 77 | 10 | 65 | 149 | 1.96532 | 105 | 221 | 0.54448 |
| -14 | 7 | 79.311 | 26 | 79 | 9.55074 | 66 | 151 | 1.89627 | 106 | 223 | 0.52912 |
| -13 | 9 | 74.536 | 27 | 81 | 9.12445 | 67 | 153 | 1.83003 | 107 | 225 | 0.51426 |
| -12 | 10 | 70.1698 | 28 | 82 | 8.71983 | 68 | 154 | 1.76647 | 108 | 226 | 0.49989 |
| -11 | 12 | 66.0898 | 29 | 84 | 8.33566 | 69 | 156 | 1.70547 | 109 | 228 | 0.486 |
| -10 | 14 | 62.2756 | 30 | 86 | 7.97078 | 70 | 158 | 1.64691 | 110 | 230 | 0.47256 |
| -9 | 16 | 58.7079 | 31 | 88 | 7.62411 | 71 | 160 | 1.59068 | 111 | 232 | 0.45957 |
| -8 | 18 | 56.3694 | 32 | 90 | 7.29464 | 72 | 162 | 1.53668 | 112 | 234 | 0.44699 |
| -7 | 19 | 52.2438 | 33 | 91 | 6.98142 | 73 | 163 | 1.48481 | 113 | 235 | 0.43482 |
| -6 | 21 | 49.3161 | 34 | 93 | 6.68355 | 74 | 165 | 1.43498 | 114 | 237 | 0.42304 |
| -5 | 23 | 46.5725 | 35 | 95 | 6.40021 | 75 | 167 | 1.38703 | 115 | 239 | 0.41164 |
| -4 | 25 | 44 | 36 | 97 | 6.13059 | 76 | 169 | 1.34105 | 116 | 241 | 0.4006 |
| -3 | 27 | 41.5878 | 37 | 99 | 5.87359 | 77 | 171 | 1.29078 | 117 | 243 | 0.38991 |
| -2 | 28 | 39.8239 | 38 | 100 | 5.62961 | 78 | 172 | 1.25423 | 118 | 244 | 0.37956 |
| -1 | 30 | 37.1988 | 39 | 102 | 5.39689 | 79 | 174 | 1.2133 | 119 | 246 | 0.36954 |
| 0 | 32 | 35.2024 | 40 | 104 | 5.17519 | 80 | 176 | 1.17393 | 120 | 248 | 0.35982 |
| 1 | 34 | 33.3269 | 41 | 106 | 4.96392 | 81 | 178 | 1.13604 | 121 | 250 | 0.35042 |
| 2 | 36 | 31.5635 | 42 | 108 | 4.76253 | 82 | 180 | 1.09958 | 122 | 252 | 0.3413 |
| 3 | 37 | 29.9058 | 43 | 109 | 4.5705 | 83 | 181 | 1.06448 | 123 | 253 | 0.33246 |
| 4 | 39 | 28.3459 | 44 | 111 | 4.38736 | 84 | 183 | 1.03069 | 124 | 255 | 0.3239 |
| 5 | 41 | 26.8778 | 45 | 113 | 4.21263 | 85 | 185 | 0.99815 | 125 | 257 | 0.31559 |
| 6 | 43 | 25.4954 | 46 | 115 | 4.04589 | 86 | 187 | 0.96681 | 126 | 259 | 0.30754 |
| 7 | 45 | 24.1932 | 47 | 117 | 3.88673 | 87 | 189 | 0.93662 | 127 | 261 | 0.29974 |
| 8 | 46 | 22.5662 | 48 | 118 | 3.73476 | 88 | 190 | 0.90753 | 128 | 262 | 0.29216 |
| 9 | 48 | 21.8094 | 49 | 120 | 3.58962 | 89 | 192 | 0.8795 | 129 | 264 | 0.28482 |
| 10 | 50 | 20.7184 | 50 | 122 | 3.45097 | 90 | 194 | 0.85248 | 130 | 266 | 0.2777 |
| 11 | 52 | 19.6891 | 51 | 124 | 3.31847 | 91 | 196 | 0.82643 | 131 | 268 | 0.27078 |
| 12 | 54 | 18.7177 | 52 | 126 | 3.19183 | 92 | 198 | 0.80132 | 132 | 270 | 0.26408 |
| 13 | 55 | 17.8005 | 53 | 127 | 3.07075 | 93 | 199 | 0.77709 | 133 | 271 | 0.25757 |
| 14 | 57 | 16.9341 | 54 | 129 | 2.95896 | 94 | 201 | 0.75373 | 134 | 273 | 0.25125 |
| 15 | 59 | 16.1156 | 55 | 131 | 2.84421 | 95 | 203 | 0.73119 | 135 | 275 | 0.24512 |
| 16 | 61 | 15.3418 | 56 | 133 | 2.73823 | 96 | 205 | 0.70944 | 136 | 277 | 0.23916 |
| 17 | 63 | 14.6181 | 57 | 135 | 2.63682 | 97 | 207 | 0.68844 | 137 | 279 | 0.23338 |
| 18 | 64 | 13.918 | 58 | 136 | 2.53973 | 98 | 208 | 0.66818 | 138 | 280 | 0.22776 |
| 19 | 66 | 13.2631 | 59 | 138 | 2.44677 | 99 | 210 | 0.64862 | 139 | 282 | 0.22231 |
Temperature sensor resistance value table for T5 (°C – -K)
| ° C | ° F | K Ohm | ° C | ° F | K Ohm | ° C | ° F | K Ohm | ° C | ° F | K Ohm |
|---|---|---|---|---|---|---|---|---|---|---|---|
| -20 | -4 | 542.7 | 20 | 68 | 68.66 | 60 | 140 | 13.59 | 100 | 212 | 3.702 |
| -19 | -2 | 511.9 | 21 | 70 | 65.62 | 61 | 142 | 13.11 | 101 | 214 | 3.595 |
| -18 | 0 | 483 | 22 | 72 | 62.73 | 62 | 144 | 12.65 | 102 | 216 | 3.492 |
| -17 | 1 | 455.9 | 23 | 73 | 59.98 | 63 | 145 | 12.21 | 103 | 217 | 3.392 |
| -16 | 3 | 430.5 | 24 | 75 | 57.37 | 64 | 147 | 11.79 | 104 | 219 | 3.296 |
| -15 | 5 | 406.7 | 25 | 77 | 54.89 | 65 | 149 | 11.38 | 105 | 221 | 3.203 |
| -14 | 7 | 384.3 | 26 | 79 | 52.53 | 66 | 151 | 10.99 | 106 | 223 | 3.113 |
| -13 | 9 | 363.3 | 27 | 81 | 50.28 | 67 | 153 | 10.61 | 107 | 225 | 3.025 |
| -12 | 10 | 343.6 | 28 | 82 | 48.14 | 68 | 154 | 10.25 | 108 | 226 | 2.941 |
| -11 | 12 | 325.1 | 29 | 84 | 46.11 | 69 | 156 | 9.902 | 109 | 228 | 2.86 |
| -10 | 14 | 307.7 | 30 | 86 | 44.17 | 70 | 158 | 9.569 | 110 | 230 | 2.781 |
| -9 | 16 | 291.3 | 31 | 88 | 42.33 | 71 | 160 | 9.248 | 111 | 232 | 2.704 |
| -8 | 18 | 275.9 | 32 | 90 | 40.57 | 72 | 162 | 8.94 | 112 | 234 | 2.63 |
| -7 | 19 | 261.4 | 33 | 91 | 38.89 | 73 | 163 | 8.643 | 113 | 235 | 2.559 |
| -6 | 21 | 247.8 | 34 | 93 | 37.3 | 74 | 165 | 8.358 | 114 | 237 | 2.489 |
| -5 | 23 | 234.9 | 35 | 95 | 35.78 | 75 | 167 | 8.084 | 115 | 239 | 2.422 |
| -4 | 25 | 222.8 | 36 | 97 | 34.32 | 76 | 169 | 7.82 | 116 | 241 | 2.357 |
| -3 | 27 | 211.4 | 37 | 99 | 32.94 | 77 | 171 | 7.566 | 117 | 243 | 2.294 |
| -2 | 28 | 200.7 | 38 | 100 | 31.62 | 78 | 172 | 7.321 | 118 | 244 | 2.233 |
| -1 | 30 | 190.5 | 39 | 102 | 30.36 | 79 | 174 | 7.086 | 119 | 246 | 2.174 |
| 0 | 32 | 180.9 | 40 | 104 | 29.15 | 80 | 176 | 6.859 | 120 | 248 | 2.117 |
| 1 | 34 | 171.9 | 41 | 106 | 28 | 81 | 178 | 6.641 | 121 | 250 | 2.061 |
| 2 | 36 | 163.3 | 42 | 108 | 26.9 | 82 | 180 | 6.43 | 122 | 252 | 2.007 |
| 3 | 37 | 155.2 | 43 | 109 | 25.86 | 83 | 181 | 6.228 | 123 | 253 | 1.955 |
| 4 | 39 | 147.6 | 44 | 111 | 24.85 | 84 | 183 | 6.033 | 124 | 255 | 1.905 |
| 5 | 41 | 140.4 | 45 | 113 | 23.89 | 85 | 185 | 5.844 | 125 | 257 | 1.856 |
| 6 | 43 | 133.5 | 46 | 115 | 22.89 | 86 | 187 | 5.663 | 126 | 259 | 1.808 |
| 7 | 45 | 127.1 | 47 | 117 | 22.1 | 87 | 189 | 5.488 | 127 | 261 | 1.762 |
| 8 | 46 | 121 | 48 | 118 | 21.26 | 88 | 190 | 5.32 | 128 | 262 | 1.717 |
| 9 | 48 | 115.2 | 49 | 120 | 20.46 | 89 | 192 | 5.157 | 129 | 264 | 1.674 |
| 10 | 50 | 109.8 | 50 | 122 | 19.69 | 90 | 194 | 5 | 130 | 266 | 1.632 |
| 11 | 52 | 104.6 | 51 | 124 | 18.96 | 91 | 196 | 4.849 | |||
| 12 | 54 | 99.69 | 52 | 126 | 18.26 | 92 | 198 | 4.703 | |||
| 13 | 55 | 95.05 | 53 | 127 | 17.58 | 93 | 199 | 4.562 | |||
| 14 | 57 | 90.66 | 54 | 129 | 16.94 | 94 | 201 | 4.426 | |||
| 15 | 59 | 86.49 | 55 | 131 | 16.32 | 95 | 203 | 4.294 | |||
| 16 | 61 | 82.54 | 56 | 133 | 15.73 | 96 | 205 | 4.167 | |||
| 17 | 63 | 78.79 | 57 | 135 | 15.16 | 97 | 207 | 4.045 | |||
| 18 | 64 | 75.24 | 58 | 136 | 14.62 | 98 | 208 | 3.927 | |||
| 19 | 66 | 71.86 | 59 | 138 | 14.09 | 99 | 210 | 3.812 |
2. Checking the compressor